T1 - Improved Thermally Activated Building System Design Method Considering Integration of Air Systems
AU - Chung, Woong June
AU - Lim, Jae Han
N1 - Publisher Copyright:
© 2018 Woong June Chung and Jae-Han Lim.
PY - 2018
Y1 - 2018
N2 - The purpose of the thermally activated building system design is to maintain the thermal comfort of the building indoor environment by securing enough thermal output of the system. For preventing the condensation on the thermally activated building system, the air system is mostly integrated with the thermally activated building system. However, the common design method in the standards only considers the thermal performance of the system itself and cannot reflect the effects of the air system. Thus, the design process of the thermally activated building system should include the consideration about the latent load and ventilation. In order to reflect the effect of the air system, the amount of sensible load removed by the thermally activated building system and air system should be included in the design process. The sensible load handled by the air system highly depends on the type of the air system and design consideration to prevent the condensation and maintain the indoor air quality. In this study, the air system choosing process was included by simulating and observing the sensible load removed by different types of the air system, and thermal performance adjustment in the design process was proposed.
AB - The purpose of the thermally activated building system design is to maintain the thermal comfort of the building indoor environment by securing enough thermal output of the system. For preventing the condensation on the thermally activated building system, the air system is mostly integrated with the thermally activated building system. However, the common design method in the standards only considers the thermal performance of the system itself and cannot reflect the effects of the air system. Thus, the design process of the thermally activated building system should include the consideration about the latent load and ventilation. In order to reflect the effect of the air system, the amount of sensible load removed by the thermally activated building system and air system should be included in the design process. The sensible load handled by the air system highly depends on the type of the air system and design consideration to prevent the condensation and maintain the indoor air quality. In this study, the air system choosing process was included by simulating and observing the sensible load removed by different types of the air system, and thermal performance adjustment in the design process was proposed.
UR - http://www.scopus.com/inward/record.url?scp=85049858601&partnerID=8YFLogxK
U2 - 10.1155/2018/4928746
DO - 10.1155/2018/4928746
M3 - Article
AN - SCOPUS:85049858601
SN - 1687-8086
VL - 2018
JO - Advances in Civil Engineering
JF - Advances in Civil Engineering
M1 - 4928746
ER -