Abstract
This study proposes a framework to integrate data center (IDC)–based fast frequency response (FFR) into power-system analysis to address frequency stability challenges under high renewable penetration. Three scenarios (2023, 2030, 2038) are developed from Korea’s 11th Basic Plan for Electricity Supply and Demand, reflecting renewable penetration and IDC demand. These scenarios are simulated on the IEEE 39-bus system, with synchronous generation reduced proportionally to represent increasing renewable penetration. To capture wind variability, wind power time series are generated from meteorological data collected near major wind farms on Jeju Island. A generator trip contingency is considered as a disturbance event. IDC participation is modeled with three strategies: no involvement, UPS-only, and UPS+IT load. Results show UPS mitigates the initial rate of change of frequency (RoCoF) and nadir drop, while UPS+IT load further raises nadir and accelerates recovery. Results highlight the potential of IDC-based FFR to offset inertia loss in renewable-dominated systems.
| Original language | English |
|---|---|
| Pages (from-to) | 4833-4844 |
| Number of pages | 12 |
| Journal | Journal of Mechanical Science and Technology |
| Volume | 40 |
| Issue number | 7 |
| DOIs | |
| State | Published - Jul 2026 |
Bibliographical note
Publisher Copyright:© The Korean Society of Mechanical Engineers and Springer-Verlag GmbH Germany, part of Springer Nature 2026.
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- Data center
- Demand response
- Fast frequency response
- Power system dynamics
- Uninterruptable power supply
Fingerprint
Dive into the research topics of 'Dynamic frequency support from data centers in power systems with high renewable penetration'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver