Design of concrete-filled hollow structural steel columns for fire endurance

Venkatesh K.R. Kodur, David H. Mackinnon

Research output: Contribution to specialist publicationArticle

52 Scopus citations

Abstract

The benefits of steel hollow structural sections (HSS) from an aesthetic and structural point of view have long been recognized by architects and engineers in Canada, and more recently in the United States. However, when building codes require structural fire protection, the cost of providing such protection can be expensive for exposed members. Filling an HSS column with concrete not only improves the capacity of the member through composite action at ambient temperatures but also provides fire endurance periods of up to 3 hours depending on the load level, section size, concrete strength and reinforcing characteristics. Physical tests and parametric studies recently completed at the National Fire Laboratory in Ottawa have resulted in design equations which predict the load carrying capacity and fire endurance period of concentrically loaded HSS columns filled with plain concrete, bar-reinforced concrete and steel fiber-reinforced concrete. The design method is presented, case studies are used to illustrate potential applications, and practical suggestions are made regarding construction techniques.

Original languageEnglish
Pages13-24
Number of pages12
Volume37
No1
Specialist publicationEngineering Journal
StatePublished - Mar 2000

Fingerprint

Dive into the research topics of 'Design of concrete-filled hollow structural steel columns for fire endurance'. Together they form a unique fingerprint.

Cite this